(!)Due to Microsoft's end of support for Internet Explorer 11 on 15/06/2022, this site does not support the recommended environment.

  • Sehubungan dengan adanya Peraturan Baru Kementerian Perdagangan No.36 Tahun 2023 tentang Pembatasan Impor Barang, MISUMI Indonesia melakukan tindakan pencegahan. Lihat informasi detailnya di sini
    Due to New Regulation of Ministry Of Trade No.36 of 2023 concerning retrictions on imports of goods, MISUMI Indonesia do precautions measure. See detail information here
  • Nomor telepon alternatif Kontak Layanan Pelanggan : 021-29182911| 021-29182991 | 021-29182997 | 021-29182998
    Alternative telephone number Contact Customer Service: 021-29182911 | 021-29182991 | 021-29182997 | 021-29182998

Temperature Controllers Standard Type

Temperature Controllers Standard Type

Click this image to zoom it.

Move the mouse over the image to zoom

  • Volume Discount

Temperature Controllers Standard Type
Temperature controllers are devices used to adjust the temperature of the controlled device to the set target temperature
[Feature]
● Input : Thermocouple (K, J, R, T, N, S, B) and Resistance thermometer (Pt100Ω / JPt100Ω.)
● Output : Relay contact output or SSR drive output free switching
● Power Supply Voltage : AC100~240VAC~50/60Hz±10%
● Mounting Size L X H (mm.) : 45 X 45
[Application]
It is used to adjust the temperature of the controlled device to the set target temperature



Temperature Controllers Product Overview

The economy series Temperature Controllers is easy to operate and learn at an affordable price. It has better temperature drift and stability than other instruments of the same class, delivering a certain energy-saving effect. It is specially designed for applications with the temperature range of 0.1-999.9 °C, such as light industrial machines and environmental refrigeration/heating equipment. Its selection, configuration and operation are simple. It has powerful performance with complete functions, and can be applied more widely. It is your ideal choice at affordable price.
Product Overview

Temperature Controllers Product Feature

1. The motherboard is equipped with the function of free switching between the SSR voltage drive output and relay contact output. Users do not need to buy 2 products with different outputs at the same time, which greatly reduces the purchase cost and improves the convenience of use.
2. The general 100~240 VAC power supply is provided.
3. We have independently developed an intelligent adjustment algorithm suitable for the functions of the FA industry with the internal operation accuracy of 0.1°C. Thus, the temperature can be controlled precisely without overshooting.
4. Input specifications: K, E, J, N and Pt100 are provided for your free selection.
5. Temperature Controllers Measurement accuracy: 0.3 Grade
6. Output specifications: G: Solid state relay (SSR) Voltage output: 5 VDC/30 mA (for driving the SSR solid state relay).
   L: Relay contact switch output (Always ON type): 250 VAC/2A or 30 VDC/2A.
7. Alarm function: Upper limit alarm, lower limit alarm, positive and negative deviation alarm, sensor disconnection alarm, and heater disconnection alarm
8. Operating environment: Temperature -10~+60℃, and humidity 0~90RH%

Disturbance performance comparison
Product Feature
Temperature Controllers Products available on the market
Large temperature change, long temperature constant time
Product Feature
MISUMI Economy Series Temperature Controller
Small temperature change, short temperature constant time
Conventional PID Control
Product Feature
Temperature Controllers Products circulating on the market
MISUMI Economy Series Intelligent PID Control
Product Feature
Temperature Controllers

Temperature Controllers Precautions

· Temperature Controllers When it is necessary to connect an extension cable for the 3-wire RTD sensor, please make sure that the material, diameter and length of the extension cable are consistent with those of the sensor cable, otherwise it will cause temperature deviation.
· Please use M3 terminal to connect AC power supply.
· To avoid interference, please separate the signal line from the power line and high-voltage line during wiring.

Temperature Controllers Usage Method

Temperature Controllers Connection Diagram
C-MTCTRS (Standard Type)
Usage Method
C-MTCTRST (including RS485 communication)
Usage Method

Temperature Controllers Brand introduction

MISUMI, the head office company, has been providing customers with various high-quality parts such as automation parts, mold parts, electronic parts, tool & consumables, etc. quickly and accurately since its establishment in Japan in 1963. By compiling product catalogs independently and establishing a marketing system for direct sales of products, a low-cost business operation mode has been created, and by making annual product plans according to customers' opinions and requirements, MISUMI brand-name products with high quality level have been continuously developed

Part Number 

CAD Data download and 3D preview are not available because the part number has not yet been determined.

  • *In order to open the CAD Data download and 3D preview screen, the part number must be fixed.
  • Please confirm the part number from "Specification / Dimension"on the left side, and then perform the CAD Data Download / 3D Preview operation.
Loading...
Part Number
C-MTCTRS
Part NumberMinimum order quantityVolume DiscountDays to Ship
1 Piece(s)Available Same day

Loading...

  1. 1

Dimensional Drawing
Dimensional Drawing
Specification Table
ItemC-MTCTRS (Standard Type)C-MTCTRST (RS485 Communication Type)
Panel Dimension48×4848×96
Control OutputRelay contact output (contact capacity AC250 V, 3 A resistance load)
or SSR drive output (DC12 V, maximum 20 mA) free switching
InputThermocouple (K·J·R·T·N·S·B) Resistance thermometer (Pt100 and JPt100)
Control MethodON/OFF, P, PI, PD and PID control
Alarm outputUpper limit alarm, lower limit alarm and positive and negative deviation range alarm
Sampling period100mS
Indication accuracy (thermocouple)Normal temperature: PV±0.3% or ±3℃ (select the larger one) ±1-digit; use it at above 200℃; PV±0.5% or ±2℃ (select the larger one) ±1-digit  
Indication accuracy (resistance thermometer)Normal temperature: PV±0.3% or ±3℃ (select the larger one) ±1-digit; use it at above 200℃; PV±0.5% or ±2℃ (select the larger one) ±1-digit  
Indication accuracy maintenance temperature rangeStandard storage: 23±10℃
Power VoltageAC100~240VAC~50/60Hz±10%

Specification Table

Basic Information

Input Thermocouple / Temperature Measuring Resistor Control Method ON-OFF Control / PID Control with Self-Tuning / PID Control with Self-Tuning / PI Control / PD Control / P Control / Thermostats Control Output Relay Contact Output / SSR Drive Voltage Output
Number of Control Points 1 Number of Input Points(pcs.) 1 Power Supply Voltage 100::240
Failure Detecting Function Heater Breakage External Size(mm) 48×48

Please check the type/dimensions/specifications of the part C-MTCTRS in the Temperature Controllers Standard Type series.

Frequently asked question (FAQ)

Question: There is no indication or output action after the instrument is powered on.
Answer: 1. Please check if there is any fault in the instrument power cable. 2. Check if the power supply and the input power supply have the same polarity.
Question: The PV window shows "HHH" or "LLL" after the instrument is powered on, indicating an abnormality.
Answer: 1. Please check if there is any fault in the instrument power cable. 2. Check if the power supply and the input power supply have the same polarity. 3. Check if the sensor is connected reversely or damaged (open circuit or short circuit).
Question: There is no output after the instrument is powered on, but the indicator light displays normally.
Answer: 1. Please check if there is any fault in the instrument power cable. 2. Check if the output mode and external load are damaged (open circuit or short circuit). 3. Check if the external load of the instrument matches.

Tech Support