(!)Due to Microsoft's end of support for Internet Explorer 11 on 15/06/2022, this site does not support the recommended environment.

  • Pembayaran dengan kartu kredit untuk sementara tidak tersedia karena kendala sistem. Sementara waktu Anda dapat meggunakan metode Pembayaran di Muka atau QRIS. Untuk informasi lebih lanjut, silakan hubungi Customer Service : TEL: 021-8984-0008 E-mail: cs@misumi.co.id. WA: 08118984008. Kami mohon maaf atas ketidaknyamanan yang terjadi.
    Credit card payments are temporarily unavailable due to system issues. Meanwhile, you can use the Advance Payment method or QRIS. For further information, please contact Customer Service: TEL: 021-8984-0008 E-mail: cs@misumi.co.id. WA: 08118984008. We apologize for any inconvenience caused.
  • Sehubungan dengan adanya Peraturan Baru Kementerian Perdagangan No.36 Tahun 2023 tentang Pembatasan Impor Barang, MISUMI Indonesia melakukan tindakan pencegahan. Lihat informasi detailnya di sini
    Due to New Regulation of Ministry Of Trade No.36 of 2023 concerning retrictions on imports of goods, MISUMI Indonesia do precautions measure. See detail information here
  • Nomor telepon alternatif Kontak Layanan Pelanggan : 021-29182911| 021-29182991 | 021-29182997 | 021-29182998
    Alternative telephone number Contact Customer Service: 021-29182911 | 021-29182991 | 021-29182997 | 021-29182998

PLC CP Series CPU Unit CP1E (CP1E-E10DR-D)

PLC CP Series CPU Unit CP1E CP1E-E10DR-D
  • Volume Discount

A CPU unit that can be easily operated without the need for referring to a manual.
[Features]
· When you begin typing an instruction using a keyboard, suggested instructions are displayed and the addresses are automatically entered.
· Easy to grasp the overall system simply by looking at the menu, making it easy to operate without referring to a manual.
· The CP1E is equipped with a peripheral (USB) port.
· Support software (computers) can be connected using commercially available USB cables.
· The transistor output type features two 100-kHz pulse outputs for high-precision position control.
· Control multiple axes with one PLC using the two 100-kHz and four 10-kHz, single-phase high-speed counters.
· *The basic models are equipped with six 10-kHz, single-phase high-speed counters.
· Specify inverter speeds via RS-485.

PDF

Part Number

Configured Part Number is shown.

CP1E-E10DR-D

CP Series CPU Unit Specifications

CP1E external appearance

CP1E external appearance

"m-h3--wysiwyg">General Specifications
TypeAC Power Supply TypeDC Power Supply Type
FormatModel CP1E-□□□S□D□-A
Model CP1E-□□□D□-A
Model CP1E-□□□S□D□-D
Model CP1E-□□□D□-D
StructureBuilt into panel type
External Shape: Height × Depth × WidthE/N/NA□□ Type
10-point input/output type (Model CP1E-E10D□-□): 90 mm (*1) × 85 mm (*2) × 66 mm
14/20 point input/output type (Model CP1E-□14/20D□-□): 90 mm (*1) × 85 mm (*2) × 86 mm
30-point input/output type (Model CP1E-□30D□-□): 90 mm (*1) × 85 mm (*2) × 130 mm
40-point input/output type (Model CP1E-□40D□-□): 90 mm (*1) × 85 mm (*2) × 150 mm
60-point input/output type (Model CP1E-N60D□-□): 90 mm (*1) × 85 mm (*2) × 195 mm
Analog built-in 20-point input/output type (Model CP1E-NA20D□-□): 90 mm (*1) × 85 mm (*2) × 130 mm
E/N□□S(1) type
14/20-point input/output type (Model CP1E-E14/20SD□-□): 90 mm (*1) × 79 mm (*2) × 86 mm
30-point input/output type (Model CP1E-□30S(1)D□-□): 90 mm (*1) × 79 mm (*2) × 130 mm
40-point input/output type (Model CP1E-□40S(1)D□-□): 90 mm (*1) × 79 mm (*2) × 150 mm
60-point input/output type (Model CP1E-□60S(1)D□-□): 90 mm (*1) × 79 mm (*2) × 195 mm
Weight10-point input/output type (Model CP1E-E10D□-□): 300 g or less
14-point input/output type (Model CP1E-□14(S)D□-□): 360 g max.
20-point input/output type (Model CP1E-□20(S)D□-□): 370 g max.
30-point input/output type (Model CP1E-□30(S□)D□-□): 600 g max.
40-point input/output type (Model CP1E-□40(S□)D□-□): 660 g max.
60-point input/output type (Model CP1E-□60(S□)D□-□): 850 g max.
Analog built-in 20-point input/output type (Model CP1E-NA20D□-□): 680 g max
Power
Supply
Specifications
Power Supply Voltage100 to 240 V AC 50/60 Hz24 V DC
Allowable Power Supply Voltage85 to 264 V AC20.4 to 26.4 V DC
Power Consumption15 VA / 100 V AC max.
25 VA/240 V AC max.
(Model CP1E-□10/14/20(S)D□-A)
9 W max. (Model CP1E-E10D□-D)
13 W max. (Model CP1E-N14/20D□-D)
50 VA/100 V AC max.
70 VA/240 V AC max.
(Model CP1E-□30/40/60(S□)D□-A, Model CP1E-NA20D□-A)
20 W max.
(Model CP1E-N30/40/60(S□)D□-D, Model CP1E-NA20D□-D) (*4)
Inrush Current120 V AC 20 A / 8 ms max. (with room temperature cold start)
240 V AC 40 A / 8 ms max. (with room temperature cold start)
24 V DC 30 A / 20 ms max. (with room temperature cold start)
External Supply Power Supply (*3)None (Model CP1E-□10/14/20(S)D□-A)
24 V DC 300 mA max. (Model CP1E-□30/40/60D□-A, Model CP1E-□30/40/60SDR-A, Model CP1E-NA20D□-A)
None
Insulation ResistanceBetween the external AC terminals and GR terminals
20 MΩ min. (500 V DC insulation resistance���)
Except between DC primary current and DC secondary current.
Dielectric StrengthBetween the external AC terminals and GR terminals
2,300 V AC 50/60 Hz for 1 min, leakage current 5 mA max.
Except between DC primary current and DC secondary current.
Power OFF Detection Time10 ms min.2 ms min.
Operating
Environment
 
Ambient Operating Temperature0 to 55°C
Ambient Operating Humidity10 to 90% RH
Operating Ambient AtmosphereMust be no corrosive gas
Ambient Storage Temperature-20 to +75°C (excluding battery)
Operating Altitude2,000 m max.
PollutionPollution degree 2 or less: conforms to JIS B3502, IEC61131-2
Noise resistanceIEC61000-4-4 compliant 2 kV (power supply line)
Overvoltage CategoryCategory II: conforms to JIS B3502, IEC61131-2
EMC Immunity LevelZone B
Vibration ResistanceJIS C60068-2-6 compliant
5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz
Acceleration of 9.8 m/s2 for 100 min in X, Y, and Z directions (10 sweeps of 10 min each = 100 min total)
Shock ResistanceJIS C60068-2-27 compliant
147 m/s2 3 times in X, Y, and Z directions
Terminal BlockFixed type (not removable)
Terminal Screw SizeM3
Approved StandardsEC directive
Grounding MethodD type grounding (No. 3 type grounding)

Note. The expansion I/O unit and expansion unit general specifications use the same conditions as for the CPU unit.
* 1. Total of 110 mm with mounting brackets
*2. Excluding cables
*3. Use the external power supply to power input devices. Do not use it to drive output devices.
* 4. This is the rated value for the maximum system configuration. Use the following formula to calculate power consumption for DC power types.
Formula:
DC power consumption = (5 V current consumption) × 5 V/70% (CP1L internal power efficiency) + (24 V current consumption) × 1.1 (current fluctuation factor)
Use the calculation result of the above to select a DC power supply allowing a sufficient margin.

  • *See the catalog for performance specifications and dimensional outline drawings.
Part Number
CP1E-E10DR-D
Part NumberMinimum order quantityVolume DiscountDays to ShipRoHSType Number of Inputs/Outputs
(Point)
Output Format Unit Type Power Supply Note 1
1 Piece(s) Same day 10Standalone10RelayBasic Model (Standard Type)DCUSB Built-In

Loading...

  1. 1
 

Please check the type/dimensions/specifications of the part CP1E-E10DR-D in the PLC CP Series CPU Unit CP1E series.

Products like this...

Part Number
CP1E-E10DR-A
CP1E-E10DT-A
CP1E-E10DT-D
CP1E-E14DR-A
CP1E-E60SDR-A
CP1E-N60DR-A
Part NumberMinimum order quantityVolume DiscountDays to ShipRoHSType Number of Inputs/Outputs
(Point)
Output Format Unit Type Power Supply Note 1
1 Piece(s) Same day 10Standalone10RelayBasic Model (Standard Type)ACUSB Built-In
1 Piece(s) Same day 10Standalone10Transistor (sync)Basic Model (Standard Type)ACUSB Built-In
1 Piece(s) Same day 10Standalone10Transistor (sync)Basic Model (Standard Type)DCUSB Built-In
1 Piece(s) Same day 10-14RelayBasic Model (Standard Type)ACUSB Built-In
1 Piece(s) Quote 10-60RelayBasic Model (Renewal Type)ACUSB Built-In
1 Piece(s) Quote 10Standalone60RelayApplication Model (Standard Type)ACRS-232C, USB Built-In

Tech Support

Factory Automation, Electronics, Tools, & MRO (Maintenance, Repair and Operations)
Tel:021-8990-4102 / FAX:021-8990-5803
8:30am - 5:30pm (Monday - Friday)