(!)Due to Microsoft's end of support for Internet Explorer 11 on 15/06/2022, this site does not support the recommended environment.

  • Sehubungan dengan adanya Peraturan Baru Kementerian Perdagangan No.36 Tahun 2023 tentang Pembatasan Impor Barang, MISUMI Indonesia melakukan tindakan pencegahan. Lihat informasi detailnya di sini
    Due to New Regulation of Ministry Of Trade No.36 of 2023 concerning retrictions on imports of goods, MISUMI Indonesia do precautions measure. See detail information here
  • Nomor telepon alternatif Kontak Layanan Pelanggan : 021-29182911| 021-29182991 | 021-29182997 | 021-29182998
    Alternative telephone number Contact Customer Service: 021-29182911 | 021-29182991 | 021-29182997 | 021-29182998

Fieldbus System (for Output), EX120/121/122 Series

Fieldbus System (for Output), EX120/121/122 Series

Fieldbus System (For Output) EX120/121/122 Series compatible with a variety of communication networks.
[Features]
· Output type for solenoid valve.

(i)Caution

  • Webpages for products currently without individual pages on this site will be released on an ad-hoc basis.
  • Refer to the manufacturer's catalog for specification and material details.
  • Product images may be representative images. Refer to the catalog for details.

PDF

Japanese Only

Fieldbus System (For Output), EX120/121/122 Series Specifications

SI Unit Model Number Notation

SI Unit model number notation image

SI Unit model number notation image

  • *1: DN1 occupied points are 16 inputs and 16 outputs. DN1-X26 occupied points are 0 inputs and 16 outputs.
  • *2: A manifold part number is not specified for this model.
    Please inquire regarding the manifold integrated type.

Specifications

Communication SpecificationsTerminating ResistorNot provided
Internal Current Consumption (Unit)100 mA or less
Environment ResistanceEnclosureIP20
Operating Temperature Range0 to +55°C (valve 8 points ON)
0 to +50℃ (valve 16 points ON)
Operating Humidity Range35 to 85% RH (No condensation)
Withstand Voltage1,500 V AC for 1 minute between external terminal and housing
Insulation Resistance500 V DC, 2 MΩ or more between external terminal and housing
ModelEX12□-SDN1EX12□-SDN1-X26EX12□-SMJ1EX12□-SCS1
EX12□-SCS2
Communication SpecificationsProtocol NameDeviceNetTMCC-LinkMade by OMRON
CompoBus/S
Version*1Release 2.0Ver. 1.10-
Communication Speed125/250/500 kbps156/625 kbps
2.5 M / 5 M / 10 Mbps
750 kbps
Configuration File*2EDS fileCSP + file-
I/O Occupation Area (No. of Inputs/No. of Outputs)16/160/1632/32
(1 station, remote I/O stations)
SCS1: 0/16
SCS2: 0/8
Power Supply VoltageFor Control11 V DC to 25 V DC15 to 30 V DC14 V DC to 26.4 V DC
For Valve24 V DC +10%/-5%
Output SpecificationsOutput FormatSink/NPN (positive common)
Number of Outputs16 pointsSCS1: 16 points
SCS2: 8 points
Connection LoadSMC solenoid valve 24 V DC, 2.1 W or less with surge voltage suppressor circuit
Output if Communication ErrorClearHold/Clear
(Switch setting)
ClearHold/Clear
(Switch setting)
StandardsCE marking
WeightEX120: 110 g or less, EX121: 140 g or less, EX122: 130 g or less
AccessoriesCommunication connector 1 pc., power supply connector 1 pc.-
  • *1: Please note that the version is subject to change.
  • *2: Configuration files can be downloaded from the manufacturer's webpage.
ModelEX12□-SUH1EX12□-SCM1EX12□-SCM3
Communication SpecificationsProtocol NameMade by NKE
Fieldbus H System
CompoNet
Communication Speed29.4 kbps93.75 kbps/1.5 Mbps/3 Mbps/4 Mbps
Configuration File-EDS file*1
I/O Occupation Area (No. of Inputs/No. of Outputs)0/16
Power Supply VoltageFor Control24 V DC ±10%
(Common power supply)
14 V DC to 26.4 V DC
For Valve24 V DC +10%/-5%
Output SpecificationsOutput FormatSink/NPN (positive common)Sink/NPN (positive common)Source/PNP (Negative common)
Number of Outputs16 points
Connection LoadSMC solenoid valve 24 V DC, 2.1 W or less with surge voltage suppressor circuit
Output if Communication ErrorClearHold/Clear (setting via network)
Standards-CE marking
WeightEX120: 110 g or less
EX121: 140 g or less
EX122: 130 g or less
EX120: 100 g or less
EX121: 120 g or less
EX122: 110 g or less (including accessories)
Accessories-Power supply connector (EX9-CP2) 1 pc.*2
  • *1: Configuration files can be downloaded from the manufacturer's webpage.
  • *2: Communication connector (for the opposite side) is not provided.

Fieldbus System (For Output), EX120/121/122 Series Dimensions

EX120

 

(Unit: mm)

 

EX120-SDN1(-X26) dimensional drawing

EX120-SDN1(-X26) dimensional drawing

 

(Unit: mm)

 

EX120-SMJ1, SCS□, SUH1 dimensional drawing

EX120-SMJ1, SCS□, SUH1 dimensional drawing

 

(Unit: mm)

 

EX120-SCM□ dimensional drawing

EX120-SCM□ dimensional drawing

EX121

 

(Unit: mm)

 

EX121-SDN1(-X26) dimensional drawing

EX121-SDN1(-X26) dimensional drawing

 

(Unit: mm)

 

EX121-SMJ1, SCS□, SUH1 dimensional drawing

EX121-SMJ1, SCS□, SUH1 dimensional drawing

 

(Unit: mm)

 

EX121-SCM□ dimensional drawing

EX121-SCM□ dimensional drawing

EX122

 

(Unit: mm)

 

EX122-SDN1(-X26) dimensional drawing

EX122-SDN1(-X26) dimensional drawing

 

(Unit: mm)

 

EX122-SMJ1, SCS□, SUH1 dimensional drawing

EX122-SMJ1, SCS□, SUH1 dimensional drawing

 

(Unit: mm)

 

EX122-SCM□ dimensional drawing

EX122-SCM□ dimensional drawing

Part Number
EX120-SCM1
EX120-SCS1
EX120-SCS2
EX120-SDN1
EX120-SMJ1
EX121-SCS1
EX121-SDN1
EX121-SMJ1
EX122-SCS1
EX122-SCS2
EX122-SDN1
EX122-SMJ1
EX122-SUH1
Part NumberMinimum order quantityVolume DiscountDays to ShipValve Interface Communication Protocol
1 Piece(s) 31 Day(s) Plug-InCompoNet NPN
1 Piece(s) 31 Day(s) Plug-InOMRON CompoBus/S (16 output)
1 Piece(s) 31 Day(s) Plug-InOMRON CompoBus/S (8 output)
1 Piece(s) 31 Day(s) Plug-InDeviceNet (16 input/16 output)
1 Piece(s) 31 Day(s) Plug-InCC-Link
1 Piece(s) 31 Day(s) Flat cable DIN rail mountingOMRON CompoBus/S (16 output)
1 Piece(s) 20 Day(s) Flat cable DIN rail mountingDeviceNet (16 input/16 output)
1 Piece(s) 31 Day(s) Flat cable DIN rail mountingCC-Link
1 Piece(s) 31 Day(s) Plug-in DIN rail mountingOMRON CompoBus/S (16 output)
1 Piece(s) 31 Day(s) Plug-in DIN rail mountingOMRON CompoBus/S (8 output)
1 Piece(s) 31 Day(s) Plug-in DIN rail mountingDeviceNet (16 input/16 output)
1 Piece(s) 31 Day(s) Plug-in DIN rail mountingCC-Link
1 Piece(s) 31 Day(s) Plug-in DIN rail mountingNKE Fieldbus H system

Loading...

  1. 1

Basic Information

Type Solenoid Output Format Sink/NPN (Positive common)

Tech Support