(!)Due to Microsoft's end of support for Internet Explorer 11 on 15/06/2022, this site does not support the recommended environment.

  • Sehubungan dengan adanya Peraturan Baru Kementerian Perdagangan No.36 Tahun 2023 tentang Pembatasan Impor Barang, MISUMI Indonesia melakukan tindakan pencegahan. Lihat informasi detailnya di sini
    Due to New Regulation of Ministry Of Trade No.36 of 2023 concerning retrictions on imports of goods, MISUMI Indonesia do precautions measure. See detail information here
  • Nomor telepon alternatif Kontak Layanan Pelanggan : 021-29182911| 021-29182991 | 021-29182997 | 021-29182998
    Alternative telephone number Contact Customer Service: 021-29182911 | 021-29182991 | 021-29182997 | 021-29182998

SPD for Power Supply Class II/III LS Series

SPD for Power Supply Class II/III LS Series

Lightning arrester that protects various low-voltage power supply circuits from lightning surges and is compatible with Class II/III (JIS C5381-11).
[Features]
・ By integrating each SPD, the wiring labor-hours can be reduced and the work time can be greatly reduced
・ Plug-in type, SPD body can be replaced independently
・ Built-in disconnection device for deterioration
・ With SPD operation display function. Supports deteriorated contact output for peace of mind even when deteriorated
[Applications]
・ Power supply protection for factories, buildings, etc.
・ Power supply protection for computers and electronic devices
・ Fire alarm power supply protection
・ Power supply protection for other low-voltage equipment

PDF

Japanese Only

Part Number

Configured Part Number is shown.

 
Part Number
LS-T1FS
LS-T2FS
LS-T4FS
LS-TE22FS
LS-TE32FS
LS-TE34FS
LS-TE42FS
LS-TL32FS
LS-TL34FS
LS-TN33FS
LS-TN42FS
LS-TN44FS
Part NumberMinimum order quantityVolume DiscountDays to ShipRoHSVoltage Type Dimension width
(mm)
Maximum Continuous Operational Voltage Voltage protection level Voltage when starting operations Protection areas
1 Piece(s) 16 Day(s) or more -100VSingle pole type18.5AC130V800V or less220V±10%-
1 Piece(s) 16 Day(s) or more -200VSingle pole type18.5AC250V1300V or less440 V±10%-
1 Piece(s) 20 Day(s) or more 10400VSingle pole type18.5AC510V2500V or less1000V±10%-
1 Piece(s) 16 Day(s) or more -200VIntegrated36.5AC250V1300V or less-L-L between
1 Piece(s) 16 Day(s) or more -200VIntegrated54.5AC250V1300V or less-L-L between
1 Piece(s) 16 Day(s) or more -400VIntegrated54.5AC510V2500V or less-L-L between
1 Piece(s) 20 Day(s) or more 10200VIntegrated72.5AC250V1300V or less-L-L between
1 Piece(s) 20 Day(s) or more 10200VIntegrated54.5AC250V1500V or less-L-L between
1 Piece(s) 20 Day(s) or more 10400VIntegrated54.5AC510V2500V or less-L-L between
1 Piece(s) 20 Day(s) or more 10100V / 200VIntegrated36.5AC130V/250V800V or lower/1500V or lower-L-N between / L-L between
1 Piece(s) 20 Day(s) or more 10100V / 200VIntegrated54.5AC130V/250V800V or lower/1500V or lower-L-N between / L-L between
1 Piece(s) 20 Day(s) or more 10200V / 400VIntegrated54.5AC250V/510V1300 V or lower/2500 V or lower-L-N between / L-L between

Loading...

  1. 1

Basic Information

Application Power Supply Mounting Method Crimp terminal attached Class, category Class II / Class III
Dimension vertical(mm) 95 Dimension depth(mm) 63.5 Nominal Discharge Current (8/20 μs) 20kA
Maximum Discharge Current (8/20 μs) 40kA

Tech Support

Factory Automation, Electronics, Tools, & MRO (Maintenance, Repair and Operations)
Tel:021-8990-4102 / FAX:021-8990-5803
8:30am - 5:30pm (Monday - Friday)